The altitude does not exceed 2000m;
The ambient air temperature is not higher than +40℃, and the average temperature within 24h is not higher than +35℃, and the surrounding air temperature is not lower than -50℃;
Atmospheric conditions: The air is clean, the relative humidity does not exceed 50% when the temperature is +40°C, and higher relative humidity is allowed when the temperature is lower, for example: +20°C is 90%;
There is no place with fire, explosion hazard, serious pollution, chemical corrosion and severe vibration;
Tilt not more than 5° to the vertical;
This product is suitable for transportation and storage at the following temperatures: -25°C ~ +55°C, within a short period of time (not more than 24h) not exceeding +70°C;
If the above conditions of use cannot be met, the user should ask the manufacturer when placing an order and negotiate a settlement.
No | Project | Technical Parameter | |
1 | Overvoltage category | Ⅳ Ⅲ | |
2 | Pollution level | 3 | |
3 | Rated insulation voltage | 660V/1000V | |
4 | Rated working voltage | 400V/660V | |
5 | Rated frequency | 50/60 Hz | |
6 | Horizontal busbar | Rated current | ≤5000A |
7 | Busbar rated short-time withstand current | 50kA,65kA,80kA(Valid values)1s | |
8 | Busbar rated peak withstand current | 105kA/0.1s,140kA/0.1s,176kA/0.1s | |
9 | Vertical busbar | Rated current | ≤1000A |
10 | Busbar rated short-time withstand current | 50kA | |
11 | Busbar rated peak withstand current | 105kA/0.1s | |
12 | Enclosure rating | IP30,IP40 |